Silica gel rotor adsorption dehumidifiers designed for medium-to-large industrial storage and process applications. With AISI 304 stainless steel housing, electric regeneration, G4 filters and PLC control, they deliver reliable humidity control between −30°C and +40°C.

Max. Capacity
5.0kg/h
Operating Range
−30 / +40°C
Models
2models
🔩AISI 304 Stainless Steel HousingElectric Regeneration🌡−30°C / +40°C
AD 800-1100 industrial desiccant rotor dehumidifier
Operating Principle

Adsorption Technology

AD series units operate on an adsorption principle using two separate air streams. Process air passes through the silica gel rotor; the silica gel absorbs water vapour from the air, drying it. As the rotor slowly turns, regeneration air is directed in the opposite direction: heated to +100°C by electric heaters, this airstream strips the absorbed moisture from the rotor, restoring its initial adsorption capacity. The moisture-laden regeneration air is then discharged to the outside.

Desiccant rotor adsorption and regeneration airflow principle
Process airProcess Air
Wet airWet Air
Dry airDry Air
Reactivation airReactivation Air
01
Process Air Inlet

Humid air passes through a G4 filter and is directed to the silica gel rotor; the fan drives the airstream using negative pressure.

02
Adsorption

The silica gel rotor adsorbs water vapour from the process air; the dried airstream is delivered to the process or conditioned space.

03
Regeneration

PTC electric heaters raise regeneration air temperature to ~100°C; this hot airstream passes through the rotor in the opposite direction, stripping and expelling moisture.

04
Continuous Cycle

The rotor slowly rotates between adsorption and regeneration zones, providing uninterrupted dehumidification.

Technical Construction

Materials & Structural Features

Housing

AISI 304 stainless steel; removable top and front panels for easy maintenance.

Silica Gel Rotor

High-efficiency silica gel rotor; low air pressure drop, long service life and consistent adsorption capacity.

Drive System

Gearmotor and belt drive system; stable operation at 6–12 rph.

Regeneration Heater

Self-regulating PTC element electric heating coil with modulating power system.

Fans

Process and regeneration fans directly coupled to IP55 / ISO F class single or three-phase motors; optional frequency converter for speed control.

Filters

Separate G4 filters on both process and regeneration air inlets; optional F5/F7/F9.

PLC Control

PLC control with touch-screen display; regeneration temperature regulation, alarm management, RH/dew point control and BMS integration.

Connections

Standard spiral duct compatible connections; process air inlet, dry air outlet, regeneration air inlet and wet air outlet.

Full Technical Specifications

Model-by-Model Technical Data

* Capacity values measured at 20°C / 60% relative humidity.

ParameterAD-800AD-1100T
Capacity (kg/h)*4.85.0
Process Airflow800 m³/h1,100 m³/h
Process Static Pressure200 Pa300 Pa
Process Fan Power0.25 kW0.37 kW
Regeneration Airflow250 m³/h250 m³/h
Regen. Static Pressure180 Pa180 Pa
Regen. Fan Power0.085 kW0.085 kW
Drive Motor Power11 VA11 VA
Regeneration TypeElectricElectric
Installed Power6.6 kW6.6 kW
Heating Coil Temp. Rise100°C100°C
Power Supply400V/3/50Hz400V/3/50Hz
Max. Power Consumption7.0 kW7.1 kW
Max. Current11.2 A11.6 A
Sound Pressure Level65 dB(A)66 dB(A)
Sound Power Level93 dB(A)94 dB(A)
Operating Temperature−30°C / +40°C−30°C / +40°C
Dimensions (A×B×C)1000×600×1000 mm1000×600×1000 mm
Weight145 kg150 kg
Process Air InletØ250 mmØ250 mm
Dry Air OutletØ200 mmØ200 mm
Regen. Air InletØ160 mmØ160 mm
Wet Air OutletØ160 mmØ160 mm

Request Product Selection Support

Share your process conditions and our engineering team will help you select the correct model, airflow and regeneration configuration.