ADP 2000-9500 Industrial Dehumidifier
Desiccant Rotor
High-capacity silica gel rotor dehumidifiers developed for large-scale industrial facilities. With AISI 304 stainless steel housing, electric and steam regeneration options, G4 filters and PLC control, they deliver high-airflow humidity control between −30°C and +40°C.

Adsorption Technology
ADP series units operate on an adsorption principle using two separate air streams. Process air passes through the silica gel rotor; the silica gel absorbs water vapour from the air, drying it. As the rotor slowly turns, regeneration air is directed in the opposite direction: heated to +100°C by electric heaters, this airstream strips the absorbed moisture from the rotor, restoring its initial adsorption capacity. The moisture-laden regeneration air is then discharged to the outside.

Humid air passes through a G4 filter and is directed to the silica gel rotor; the fan drives the airstream using negative pressure.
The silica gel rotor adsorbs water vapour from the process air; the dried airstream is delivered to the process or conditioned space.
Electric heaters raise regeneration air temperature to ~100°C; this hot airstream passes through the rotor in the opposite direction, stripping and expelling moisture.
The rotor slowly rotates between adsorption and regeneration zones, providing uninterrupted dehumidification.
Materials & Structural Features
AISI 304 stainless steel; high resistance to corrosive environments and industrial process conditions.
High-efficiency silica gel rotor with a honeycomb structure of corrugated heat-resistant sheets, providing a large adsorption surface and low air pressure drop. Operates undamaged in saturated air conditions; non-combustible and non-flammable.
Gearmotor and belt drive system; rotates the rotor at a slow, stable speed. Rotor shaft is fitted with ball bearings and manufactured from steel.
Electric: steel element star-connected coil; 2+ stage power modulation or PWM continuous modulation. Steam (optional): AISI 304 stainless steel tube steam coil with modulating 2-way valve.
Process and regeneration fans directly coupled to IP55 / ISO F class single or three-phase motors; optional frequency converter for speed control.
Separate G4 filters on both process and regeneration air inlets; optional F5/F7/F9.
PLC control with touch-screen display; regeneration temperature regulation, alarm management, RH/dew point control and BMS integration.
Standard spiral duct compatible connections; process air inlet, dry air outlet, regeneration air inlet and wet air outlet.
Model-by-Model Technical Data
* Capacity values measured at 20°C / 60% relative humidity.
| Parameter | ADP-2000 | ADP-3500 | ADP-5000 | ADP-6500 | ADP-8000 | ADP-9500 |
|---|---|---|---|---|---|---|
| Capacity (kg/h)* | 18.6 | 31.1 | 42.5 | 55.9 | 66.0 | 77.1 |
| Process Airflow | 2,000 m³/h | 3,500 m³/h | 5,000 m³/h | 6,500 m³/h | 8,000 m³/h | 9,500 m³/h |
| Process Static Pressure | 400 Pa | 400 Pa | 400 Pa | 400 Pa | 400 Pa | 400 Pa |
| Process Fan Power | 1.1 kW | 1.5 kW | 2.2 kW | 4.0 kW | 5.5 kW | 7.5 kW |
| Regeneration Airflow | 700 m³/h | 1,200 m³/h | 1,700 m³/h | 2,200 m³/h | 2,600 m³/h | 3,100 m³/h |
| Regen. Static Pressure | 400 Pa | 400 Pa | 400 Pa | 400 Pa | 350 Pa | 350 Pa |
| Regen. Fan Power | 0.75 kW | 0.75 kW | 1.1 kW | 1.5 kW | 1.5 kW | 2.2 kW |
| Drive Motor Power | 10 W | 10 W | 10 W | 10 W | 10 W | 10 W |
| Regeneration Type | Electric | Electric | Electric | Electric | Electric | Electric |
| Installed Power (Electric) | 25.5 kW | 39.6 kW | 56.1 kW | 72.6 kW | 85.8 kW | 99.0 kW |
| Steam Coil Power | 24.2 kW | 41.2 kW | 58.6 kW | 75.5 kW | 89.7 kW | 106.5 kW |
| Steam Consumption (6 bar) | 36 kg/h | 61 kg/h | 86 kg/h | 111 kg/h | 133 kg/h | 158 kg/h |
| Heating Coil Temp. Rise | 100°C | 100°C | 100°C | 100°C | 100°C | 100°C |
| Power Supply | 400V/3/50Hz | 400V/3/50Hz | 400V/3/50Hz | 400V/3/50Hz | 400V/3/50Hz | 400V/3/50Hz |
| Max. Power Consumption | 27.4 kW | 41.9 kW | 59.4 kW | 78.1 kW | 92.8 kW | 108.7 kW |
| Max. Current | 43.9 A | 66.8 A | 93.9 A | 121.8 A | 145.7 A | 172.3 A |
| Sound Pressure Level | 60 dB(A) | 64 dB(A) | 65 dB(A) | 66 dB(A) | 69 dB(A) | 70 dB(A) |
| Sound Power Level | 88 dB(A) | 92 dB(A) | 93 dB(A) | 94 dB(A) | 97 dB(A) | 98 dB(A) |
| Operating Temperature | −30°C / +40°C | −30°C / +40°C | −30°C / +40°C | −30°C / +40°C | −30°C / +40°C | −30°C / +40°C |
| Dimensions (A×B×C) | 1610×1000×1875 mm | 1710×1100×1975 mm | 1710×1100×1975 mm | 1810×1200×2075 mm | 1810×1200×2075 mm | 1810×1200×2075 mm |
| Weight | 490 kg | 550 kg | 590 kg | 690 kg | 710 kg | 730 kg |
| Process Air Inlet | 850×500 mm | 950×600 mm | 950×600 mm | 1,000×600 mm | 1,000×600 mm | 1,000×600 mm |
| Dry Air Outlet | 850×500 mm | 950×600 mm | 950×600 mm | 1,000×600 mm | 1,000×600 mm | 1,000×600 mm |
| Regen. Air Inlet | 600×400 mm | 600×400 mm | 600×400 mm | 600×400 mm | 600×400 mm | 600×400 mm |
| Wet Air Outlet | 370×200 mm | 370×200 mm | 370×200 mm | 370×200 mm | 370×200 mm | 370×200 mm |
Live psychrometric values for your location.
Applications Using This Product
Related Technical Articles
Request Product Selection Support
Share your process conditions and our engineering team will help you select the correct model, airflow and regeneration configuration.