Engineering Guide

The psychrometric chart is the standard HVAC engineering tool for reading the thermodynamic state of moist air on a single graph. It visualises the relationship between temperature, relative humidity, absolute humidity, dew point and enthalpy; it makes humidification, dehumidification, cooling, heating and mixing processes readable as graphical paths. This guide is a practical reading manual for engineers who want to use the chart in the field.

7 Properties on One Chart
Temperature, RH, x, dew point, wet-bulb, enthalpy and specific volume on the same graph.
Process Visualisation
Humidification, heating and cooling shown as arrows on the chart.
Capacity Reading
Δx is read off the chart and the humidification capacity is verified directly.
In this guide: the main axes of the psychrometric chart, locating an air state, drawing the humidification process, heating-then-humidify, cooling-and-dehumidification linked with humidification, comparison of steam and adiabatic processes on the chart, reading capacity off the chart, common field mistakes and the NKT engineering toolkit.

What Is a Psychrometric Chart?

The psychrometric chart is a 2D graphical tool that visualises every thermodynamic property of moist air at a given pressure. The horizontal axis is typically dry-bulb temperature (°C) and the vertical axis is absolute humidity (g/kg or kg/kg). The curves and lines on the chart let you read, for any single air state, the relative humidity (%RH), wet-bulb temperature, dew point, enthalpy and specific volume.

The value of the chart for HVAC engineering is not just easy reading, it is the ability to draw physical processes (humidification, heating, cooling, mixing) as visible paths. An arrow from one point to another shows exactly what change is taking place. The capacity number read off the chart matches the formula-based result; the visual reading speeds up understanding and error detection.

Historical note The foundations were laid by Willis Carrier in the early 1900s; today the psychrometric chart is the core tool of the ASHRAE Handbook and international HVAC standards. The Mollier chart (common in Europe) and the Carrier chart (common in the US; both are used in Türkiye) differ in axis layout but carry the same information.

Main Axes of the Chart

Reading a psychrometric chart correctly requires familiarity with seven curve groups.

Curve / AxisDirectionSymbol / UnitDescription
Dry-bulb temperatureHorizontal (bottom)T_db, °CStandard thermometer reading
Humidity ratio (absolute humidity)Vertical (right)x, g/kgMass of water vapour per kg of dry air
Relative humidity curvesCurves below saturationRH, %10%, 20%, ..., 100% (saturation curve)
Wet-bulb linesSloping from saturation to the leftT_wb, °CConstant wet-bulb temperature lines
Dew pointHorizontal from saturationT_dp, °CTemperature where condensation starts
Enthalpy linesSloping outside saturationh, kJ/kgTotal energy content
Specific volumeSloping left to rightv, m³/kgVolume per kg of air

The saturation curve (100% RH) is the most critical reference, air cannot exist above this curve; reaching it triggers condensation. Relative-humidity curves run below saturation as proportional copies of it; the vertical gap between them widens as temperature rises. Constant wet-bulb lines and constant enthalpy lines are practically very close (psychrometric identity) and are treated as the same line, especially for adiabatic processes.

Figure 1: Simplified Psychrometric Chart: Axes and Reading Lines

100% RH (saturation) 80% 60% 40% 20% −10 −5 0 5 15 22 28 35 40 Dry-Bulb Temperature (°C) 0 5 10 15 20 25 Humidity Ratio (g/kg) A: 22 °C, 50% RH x ≈ 8.2 g/kg Dew point ≈ 11 °C Reading Legend Saturation curve (100%) Relative humidity curves Reading lines (T, x) Dew-point reading Simplified schematic: a real chart also includes enthalpy and specific volume curves

Locating an Air State on the Chart

To locate an air state on the chart, two independent properties are sufficient. The most common pair is dry-bulb temperature + relative humidity; but temperature + dew point, temperature + wet-bulb, or absolute humidity + temperature also work.

For instance, to locate 22 °C / 50% RH: mark 22 °C on the horizontal axis, go up vertically; the intersection with the 50% RH curve is point A. From this point a horizontal line to the right axis reads off the absolute humidity (≈8.2 g/kg). From the same point, a horizontal line to the saturation curve gives the dew-point temperature (≈11 °C). Following the sloping enthalpy line gives the total energy content (≈43 kJ/kg).

Practical rule An air state is defined by two independent properties. Dry-bulb + RH, dry-bulb + wet-bulb (a psychrometer) and dry-bulb + dew point are all valid pairs. The pair that is not independent is dew point + humidity ratio: both depend only on the vapour partial pressure, so they describe the same horizontal line on the chart. In the field the most common pair is temperature + RH, since one hygrometer reports both.

How Humidification Looks on the Chart

Humidification is the addition of moisture, so on the chart the air state moves upward from its starting point. The direction is set by the type of humidification.

Steam humidification (for example a resistive steam humidifier or a steam-to-steam system fed by plant steam) injects steam generated at about 100 °C, so the process is practically vertical; dry-bulb temperature changes by only a few tenths of a degree while absolute humidity rises significantly. This makes steam humidification ideal for applications with strict indoor temperature specifications (printing, museums, precision manufacturing).

Adiabatic humidification (atomising, wetted media) introduces water at ambient temperature; the latent heat needed for evaporation is drawn from the air itself. So the process follows the constant-enthalpy (wet-bulb) line up and to the left, absolute humidity rises while temperature falls. In summer this provides an evaporative cooling effect; but if the indoor temperature must be held, the heat drawn from the air has to be returned by reheat.

Figure 2: Steam vs Adiabatic Humidification: Comparison on the Chart

80% 60% 40% 20% Start (5 °C, 30%) x ≈ 1.6 g/kg Steam (vertical: x ↑, T ≈ const.) Steam end (5 °C, ≈85%) x ≈ 4.6 g/kg Adiabatic (constant enthalpy, T ↓ x ↑) Adiabatic end (0 °C, ~100%) Heated (22 °C, 10%) Heating (constant x) Target (22 °C, 40%) x ≈ 6.6 g/kg −10 −5 0 5 15 22 28 35 40 Dry-Bulb Temperature (°C) 0 5 10 15 Humidity Ratio (g/kg) Steam (blue): vertical, T constant · Adiabatic (green): constant enthalpy, T drops · Heating + Steam (orange+blue): winter scenario

Heating-Then-Humidify Process

In winter, conditioning outdoor air for use takes two steps: first heat, then humidify. On the chart these two steps are read clearly and drawn together.

Example: outdoor air arrives at 5 °C / 30% RH (≈1.6 g/kg). It is first run through a heating coil and brought to 22 °C. In this step, absolute humidity does not change (no water is added), temperature rises, and relative humidity drops dramatically, the new state is 22 °C / 10% RH (still 1.6 g/kg). On the chart this is a horizontal arrow to the right. In the second step the humidifier brings the absolute humidity to target (e.g. 40% RH at 22 °C ≈ 6.6 g/kg); steam draws a vertical-up line, adiabatic draws a sloping line up and to the left.

StepProcessT (°C)RH (%)x (g/kg)Direction on Chart
1. Outdoor airInlet5301.6Starting point
2. After heatingConstant x22~101.6Horizontal right
3. After steam humidificationx rises, T constant≈22406.6Vertical up
3-alt. After adiabatic humidificationx rises, T falls≈10≈906.6Constant enthalpy (up-left)
Critical correction for adiabatic After adiabatic humidification the indoor air does not reach the 22 °C target; an additional reheat coil is required. So adiabatic systems are usually built as "preheat + adiabatic + reheat" three-step designs. With steam, a single heat + humidify pass is enough.

Cooling, Dehumidification and Humidification Link

The chart's strength is not limited to humidification, cooling + dehumidification can be read on the same chart. In summer outdoor air is hot and humid (e.g. 32 °C / 65% RH ≈ 19.5 g/kg, dew point ≈ 24.6 °C). Air passing a cooling coil first cools at constant humidity ratio, moving left on the chart; once it reaches the dew point, condensation begins and the humidity ratio falls. On a real coil this path is drawn as an approximately straight line from the inlet state towards the coil surface temperature.

In industrial use the two processes typically work together: cooling + dehumidification in summer, heating + humidification in winter. Both cycles inside the same AHU are planned on the psychrometric chart; setpoint shifts at seasonal transitions can be verified instantly.

Integrated HVAC design Modern AHU design treats the cooling coil, dehumidifier and humidifier on the same chart as a single integrated system. In hospitals, pharma, museums and data centres that require year-round constant RH, this approach is the foundation of operational continuity.

Steam vs Adiabatic on the Chart

Once the chart shows how the two humidification types differ, the comparison table below guides selection.

CriterionSteam HumidificationAdiabatic Humidification
Working principleWater injected as steam (~100 °C)Water atomised/evaporated (ambient T)
Temperature impactNegligible (T constant)Significant drop (~2.5 °C / g/kg)
Humidity impactAbsolute humidity risesAbsolute humidity rises (same Δx)
Direction on chartVertical up (T constant, x rises)Constant enthalpy (up-left, T falls)
Energy consumption~0.75 kWh / kg (electric steam)Low pump energy; if indoor temperature is held, the ≈0.68 kWh/kg drawn from the air is returned by reheat
Hygiene / sterilityHigh (steam is generated by boiling)Depends on water (RO/UV needed)
Setpoint bandTight (down to ±1% RH for resistive units; Neptronic data)Wider (typically ±3–5% RH)
Typical usePrinting, museum, hospital, pharma, precisionTextile, warehouse, data centre, hybrid cooling

Steam: When?

  • Strict indoor temperature spec (printing, museum)
  • Hygiene critical (hospital, pharma, food)
  • Setpoint band ±2% or tighter
  • Year-round humidification need
  • Winter peak dominates

Adiabatic: When?

  • Summer cooling + winter humidification combo
  • Large halls with high airflow
  • Energy efficiency primary
  • Setpoint band flexible (±5% or wider)
  • Textile, warehouse, hybrid data centre

Reading Capacity From the Chart

Humidification capacity is computed from the Δx delta read between two points on the chart. After the start and target points are marked, their absolute humidity values are read on the vertical axis and subtracted.

Example: starting at 22 °C / 30% RH (x ≈ 4.9 g/kg) and going to 22 °C / 50% RH (x ≈ 8.2 g/kg) requires Δx ≈ 3.3 g/kg. At 10,000 m³/h airflow the capacity is: ṁ = ρ × V̇ × Δx = 1.2 × 10,000 × 0.0033 ≈ 40 kg/h. Adding a 20% service margin gives a selection capacity of about 48 kg/h. The same answer is obtained from the formula or by reading the chart.

ṁ_steam = ρ_air × V̇_air × Δx_chart
StepAction on the ChartOutput
1Mark the starting point (T_in, RH_current)x_current
2Mark the target point (T_in, RH_target)x_target
3Read the vertical distance (humidity-ratio difference) between themΔx (g/kg)
4Apply ρ × V̇ × Δxṁ_steam (kg/h)
5Add a 15–25% (typically 20%) service marginSelection capacity

Common Field Mistakes

Common misreadings of the chart in the field translate directly into wrong engineering decisions. The list below summarises the most frequent interpretation errors seen in the field.

MistakeOutcomeCorrect Approach
Treating RH delta as mass directlyWrong capacityConvert to absolute humidity first, then take Δx
Confusing dew point with wet-bulbCooling coil mis-sizedRead each property separately
Design point above the saturation curveNon-physical, condensation occursLimit duct supply RH to 85–90% with a high-limit humidistat
Drawing adiabatic verticalTemperature drop ignoredDraw along constant enthalpy (up-left)
Treating steam as constant-enthalpySteam energy ignoredDraw vertical (T constant)
Skipping the mixed-air stateOutdoor-air impact missedMark intermediate point from mix ratio
Using summer design for winter capacityInsufficient at peakSeparate design points per season
The most critical error A design point above the saturation curve is physically impossible, fog or condensation occurs. The design point must stay at a safe distance from the saturation curve; in a duct receiving steam, the supply-air RH is typically limited to 85–90% RH by a high-limit humidistat at the end of the duct. To read this distance as a temperature difference, check the dew point: at 22 °C, 90% RH has a dew point of about 20.3 °C, only 1.7 K from saturation. Sensor placement and hygroscopic material effects must also be evaluated during design.

NKT Portal and Psychrometric Tools

NKT – Nem Kontrol Teknolojileri uses the psychrometric chart in device selection and supply not only as a reading tool but as a visual checkpoint for the selection decision. Showing the start and target points on the chart clarifies technical communication with the customer and prevents misunderstandings.

The psychrometric calculator on the NKT website (absolute humidity, dew point, enthalpy) uses the same equations and produces results consistent with the chart. When temperature and RH measured at an existing site are plotted on the chart, the actual operating point can be compared with the design target and the device selection checked against that difference.

NKT selects and supplies the Neptronic humidifier family that suits the application (resistive SKE4, steam-to-steam SKS4 and high-pressure atomisation SKH). In static-electricity-sensitive ESD production areas, museums and archives, and tight-spec print halls, correct device selection is the basis of operational continuity.

The psychrometric chart is the visual language of humidification system design. Knowing how to locate an air state on the chart, how humidification processes are drawn (steam vertical, adiabatic constant-enthalpy), and how heating and cooling steps integrate, is core engineering literacy for correct device selection and capacity sizing.

Reading capacity off the chart is the visual verification of the formula calculation; both methods give the same number, but the chart speeds up understanding and error detection. Using chart-based visualisation together with numerical calculation makes the device-selection decision transparent and strengthens technical communication with the customer.

For support in selecting the right device for your facility, contact us. The design conditions and measured values you share are evaluated on the chart, and a steam, adiabatic or hybrid device selection and supply proposal follows.