AD 1000-3100 Industrial Dehumidifier
Desiccant Rotor
Silica gel rotor adsorption dehumidifiers designed for large-scale industrial process and manufacturing applications. AISI 304 stainless steel housing, electric and steam regeneration options, G4 filters and PLC control with touch-screen display.

Adsorption Technology
AD series units operate on an adsorption principle using two separate air streams. Process air passes through the silica gel rotor; the silica gel absorbs water vapour from the air, drying it. As the rotor slowly turns, regeneration air is directed in the opposite direction: heated to +100°C by electric heaters, this airstream strips the absorbed moisture from the rotor, restoring its initial adsorption capacity. The moisture-laden regeneration air is then discharged to the outside.

Humid air passes through a G4 filter and is directed to the silica gel rotor; the fan drives the airstream using negative pressure.
The silica gel rotor adsorbs water vapour from the process air; the dried airstream is delivered to the process or conditioned space.
PTC electric heaters raise regeneration air temperature to ~100°C; this hot airstream passes through the rotor in the opposite direction, stripping and expelling moisture.
The rotor slowly rotates between adsorption and regeneration zones, providing uninterrupted dehumidification.
Materials & Structural Features
AISI 304 stainless steel; removable top and front panels for easy maintenance.
High-efficiency silica gel rotor; low air pressure drop, long service life and consistent adsorption capacity.
Gearmotor and belt drive system; stable operation at 6–12 rph.
Electric: steel element star-connected heating coil; 2, 3 or more sequential stages for power modulation. Steam (optional): AISI 304 stainless steel tube steam coil with modulating 2-way valve.
Process and regeneration fans directly coupled to IP55 / ISO F class single or three-phase motors; optional frequency converter for speed control.
Separate G4 filters on both process and regeneration air inlets; optional F5/F7/F9.
PLC control with touch-screen display; regeneration temperature regulation, alarm management, RH/dew point control and BMS integration.
Standard spiral duct compatible connections; process air inlet, dry air outlet, regeneration air inlet and wet air outlet.
Model-by-Model Technical Data
* Capacity values measured at 20°C / 60% relative humidity.
| Parameter | AD-1000 | AD-1500 | AD-2000 | AD-2500 | AD-3100T |
|---|---|---|---|---|---|
| Capacity (kg/h)* | 8.8 | 12.7 | 15.8 | 18.9 | 11.5 |
| Process Airflow | 1,000 m³/h | 1,500 m³/h | 2,000 m³/h | 2,500 m³/h | 3,100 m³/h |
| Process Static Pressure | 300 Pa | 200 Pa | 250 Pa | 300 Pa | 250 Pa |
| Process Fan Power | 0.37 kW | 0.49 kW | 0.92 kW | 1.25 kW | 1.25 kW |
| Regeneration Airflow | 350 m³/h | 500 m³/h | 680 m³/h | 820 m³/h | 450 m³/h |
| Regen. Static Pressure | 180 Pa | 250 Pa | 180 Pa | 250 Pa | 250 Pa |
| Regen. Fan Power | 0.24 kW | 0.37 kW | 0.49 kW | 0.72 kW | 0.37 kW |
| Drive Motor Power | 11 VA | 11 VA | 11 VA | 11 VA | 11 VA |
| Regeneration Type | Electric | Electric | Electric | Electric | Electric |
| Installed Power (Electric) | 12.0 kW | 18.0 kW | 22.5 kW | 27.0 kW | 15.0 kW |
| Steam Coil Power | 12.0 kW | 17.2 kW | 23.2 kW | 28.2 kW | 15.5 kW |
| Steam Consumption (6 bar) | 21 kg/h | 30 kg/h | 40 kg/h | 49 kg/h | 27 kg/h |
| Heating Coil Temp. Rise | 100°C | 100°C | 100°C | 100°C | 100°C |
| Power Supply | 400V/3/50Hz | 400V/3/50Hz | 400V/3/50Hz | 400V/3/50Hz | 400V/3/50Hz |
| Max. Power Consumption | 12.6 kW | 18.9 kW | 23.9 kW | 29.0 kW | 16.6 kW |
| Max. Current | 18.4 A | 27.5 A | 34.8 A | 42.5 A | 24.3 A |
| Sound Pressure Level | 64 dB(A) | 64 dB(A) | 66 dB(A) | 66 dB(A) | 68 dB(A) |
| Sound Power Level | 92 dB(A) | 92 dB(A) | 94 dB(A) | 94 dB(A) | 96 dB(A) |
| Operating Temperature | −30°C / +40°C | −30°C / +40°C | −30°C / +40°C | −30°C / +40°C | −30°C / +40°C |
| Dimensions (A×B×C) | 1285×845×1255 mm | 1285×845×1255 mm | 1285×845×1255 mm | 1285×845×1255 mm | 1285×845×1255 mm |
| Weight | 205 kg | 210 kg | 215 kg | 220 kg | 230 kg |
| Process Air Inlet | 420×615 mm | 420×615 mm | 420×615 mm | 420×615 mm | 420×615 mm |
| Dry Air Outlet | 420×615 mm | 420×615 mm | 420×615 mm | 420×615 mm | 420×615 mm |
| Regen. Air Inlet | 220×350 mm | 220×350 mm | 220×350 mm | 220×350 mm | 220×350 mm |
| Wet Air Outlet | Ø250 mm | Ø250 mm | Ø250 mm | Ø250 mm | Ø250 mm |
Live psychrometric values for your location.
Applications Using This Product
Request Product Selection Support
Share your process conditions and our engineering team will help you select the correct model, airflow and regeneration configuration.