AD 3000-6500 Industrial Dehumidifier
Desiccant Rotor
Silica gel rotor adsorption dehumidifiers designed for high-capacity industrial facilities, large production areas and critical process environments. AISI 304 stainless steel housing, electric and steam regeneration options, PLC control with touch-screen display.

Adsorption Technology
AD series units operate on an adsorption principle using two separate air streams. Process air passes through the silica gel rotor; the silica gel absorbs water vapour from the air, drying it. As the rotor slowly turns, regeneration air is directed in the opposite direction: heated to +100°C by electric heaters, this airstream strips the absorbed moisture from the rotor, restoring its initial adsorption capacity. The moisture-laden regeneration air is then discharged to the outside.

Humid air passes through a G4 filter and is directed to the silica gel rotor; the fan drives the airstream using negative pressure.
The silica gel rotor adsorbs water vapour from the process air; the dried airstream is delivered to the process or conditioned space.
PTC electric heaters raise regeneration air temperature to ~100°C; this hot airstream passes through the rotor in the opposite direction, stripping and expelling moisture.
The rotor slowly rotates between adsorption and regeneration zones, providing uninterrupted dehumidification.
Materials & Structural Features
AISI 304 stainless steel; removable top and front panels for easy maintenance.
High-efficiency silica gel rotor; low air pressure drop, long service life and consistent adsorption capacity.
Gearmotor and belt drive system; stable operation at 6–12 rph.
Electric: steel element star-connected heating coil; 2, 3 or more sequential stages for power modulation. Steam (optional): AISI 304 stainless steel tube steam coil with modulating 2-way valve.
Process and regeneration fans directly coupled to IP55 / ISO F class single or three-phase motors; optional frequency converter for speed control.
Separate G4 filters on both process and regeneration air inlets; optional F5/F7/F9.
PLC control with touch-screen display; regeneration temperature regulation, alarm management, RH/dew point control and BMS integration.
Standard spiral duct compatible connections; process air inlet, dry air outlet, regeneration air inlet and wet air outlet.
Model-by-Model Technical Data
* Capacity values measured at 20°C / 60% relative humidity.
| Parameter | AD-3000 | AD-3500 | AD-4500T | AD-4000 | AD-5000 | AD-6500T |
|---|---|---|---|---|---|---|
| Capacity (kg/h)* | 23.0 | 27.3 | 21.1 | 31.7 | 37.2 | 27.1 |
| Process Airflow | 3,000 m³/h | 3,500 m³/h | 4,500 m³/h | 4,000 m³/h | 5,000 m³/h | 6,500 m³/h |
| Process Static Pressure | 400 Pa | 350 Pa | 300 Pa | 400 Pa | 400 Pa | 400 Pa |
| Process Fan Power | 1.65 kW | 1.65 kW | 2.4 kW | 2.2 kW | 2.2 kW | 4.0 kW |
| Regeneration Airflow | 900 m³/h | 1,100 m³/h | 900 m³/h | 1,350 m³/h | 1,600 m³/h | 1,100 m³/h |
| Regen. Static Pressure | 200 Pa | 300 Pa | 300 Pa | 400 Pa | 350 Pa | 400 Pa |
| Regen. Fan Power | 0.49 kW | 0.72 kW | 0.72 kW | 0.75 kW | 1.1 kW | 0.75 kW |
| Drive Motor Power | 10 W | 10 W | 10 W | 10 W | 10 W | 10 W |
| Regeneration Type | Electric | Electric | Electric | Electric | Electric | Electric |
| Installed Power (Electric) | 30.0 kW | 36.0 kW | 27.0 kW | 45.0 kW | 54.0 kW | 36.0 kW |
| Power Supply | 400V/3/50Hz | 400V/3/50Hz | 400V/3/50Hz | 400V/3/50Hz | 400V/3/50Hz | 400V/3/50Hz |
| Max. Power Consumption | 32.3 kW | 38.5 kW | 30.3 kW | 48.1 kW | 57.5 kW | 40.9 kW |
| Max. Current | 46.7 A | 55.8 A | 43.7 A | 69.5 A | 83.1 A | 60.8 A |
| Sound Pressure Level | 68 dB(A) | 68 dB(A) | 69 dB(A) | 70 dB(A) | 72 dB(A) | 73 dB(A) |
| Sound Power Level | 96 dB(A) | 96 dB(A) | 97 dB(A) | 98 dB(A) | 100 dB(A) | 101 dB(A) |
| Operating Temperature | −30°C / +40°C | −30°C / +40°C | −30°C / +40°C | −30°C / +40°C | −30°C / +40°C | −30°C / +40°C |
| Dimensions (A×B×C) | 1500×1020×1395 mm | 1500×1020×1395 mm | 1500×1020×1395 mm | 1895×1115×1500 mm | 1895×1115×1500 mm | 1895×1115×1500 mm |
| Weight | 350 kg | 360 kg | 360 kg | 490 kg | 530 kg | 545 kg |
| Process Air Inlet | 825×500 mm | 825×500 mm | 825×500 mm | 800×520 mm | 800×520 mm | 800×520 mm |
| Dry Air Outlet | 825×500 mm | 825×500 mm | 825×500 mm | 800×520 mm | 800×520 mm | 800×520 mm |
| Regen. Air Inlet | 355×290 mm | 355×290 mm | 355×290 mm | 415×350 mm | 415×350 mm | 415×350 mm |
| Wet Air Outlet | Ø280 mm | Ø280 mm | Ø280 mm | Ø315 mm | Ø315 mm | Ø315 mm |