SERVICE & MAINTENANCEDesiccant Dehumidification
AD Series Periodic Maintenance
AD series silica gel rotor dehumidifiers depend on regular maintenance to run efficiently. In this episode we cover filter checks, the white service light, the rotor, belt, seals, motors and heater, and the manufacturer's 6, 12 and 36-month maintenance schedule, based on the manufacturer's manual.
Published: 2 November 2026Narration: Turkish and English3:49
In this video
- Before maintenance, switch the unit off, wait at least 15 minutes for the heater to cool and lock the main switch; the unit can restart by itself after a power cut.
- There are two separate G4 filters for process and regeneration air, checked at least monthly. Never run the unit without filters; doing so damages the rotor.
- The white service light means a filter change or general service is due; the reason is shown on the display.
- The rotor is not replaced as a precaution; a capacity check decides. Check belt tension and seals regularly and inspect the heating coil at least twice a year.
- Schedule: every 6 months / 4000 h filter inspection and function check; every 12 months capacity check, rotor inspection, panel and calibration; every 36 months / 24,000 h belt, belt stop and rotor seals, plus safety thermostats on electric units.
More from this series
Service & Maintenance
Installing an AD Series Dehumidifier
Desiccant Dehumidification · 2 November 2026
Service & Maintenance
Commissioning the AD Series
Desiccant Dehumidification · 2 November 2026
Service & Maintenance
AD Series Troubleshooting
Desiccant Dehumidification · 2 November 2026
Service & Maintenance
Setting Up a Portable Dehumidifier
Portable Dehumidification · 1 November 2026
Service & Maintenance
Maintaining a Portable Dehumidifier
Portable Dehumidification · 1 November 2026
Service & Maintenance
Maintaining a Pool Dehumidifier
Pool Dehumidification · Maintenance · 1 November 2026