SERVICE & MAINTENANCEDesiccant Dehumidification

Commissioning the AD Series

How well an AD series silica gel rotor dehumidifier performs on site depends on the checks made at first start-up and on correctly set airflows. In this episode we cover the pre-checks, phase sequence, operating modes, setting the process and regeneration airflows, steam and hot water coils, humidity control and the performance check, based on the manufacturer's manual.

Published: 2 November 2026Narration: Turkish and English4:26

In this video

  • Commissioning is carried out by the authorised service and is a condition of the warranty. First check inside the unit, the dampers, ducts, filters and fan impellers.
  • If the white service light is on but the touch display stays dark, the phase sequence is wrong; swap two phases. The phase relay's yellow light confirms the correct sequence.
  • The process airflow is measured by the differential pressure across the unit and compared with the factory value; airflows are never set above nominal.
  • For the regeneration airflow, run the unit at full capacity for 10–15 minutes; the difference between the regeneration inlet and the regeneration temperature on the display should be about 95 ± 5 °C. The steam valve actuator must take at least 120 seconds to open.
  • With an external humidistat, stage one runs regeneration at 50% and stage two at 100%. At 20 °C / 60% inlet air the AD1000 removes 8.8 kg/h and the AD5000 37.2 kg/h; readings are recorded on the commissioning report.

Related

More from this series

Installing an AD Series Dehumidifier4:12
Service & Maintenance
Installing an AD Series Dehumidifier

The AD series are silica gel rotor industrial dehumidifiers that run continuously in production areas and warehouses where low humidity is needed. In this episode we cover safety, handling, delivery, positioning, service clearances, duct connections and the electrical supply for models AD1000 to AD6500, based on the manufacturer's manual.

Desiccant Dehumidification · 2 November 2026
AD Series Periodic Maintenance3:49
Service & Maintenance
AD Series Periodic Maintenance

AD series silica gel rotor dehumidifiers depend on regular maintenance to run efficiently. In this episode we cover filter checks, the white service light, the rotor, belt, seals, motors and heater, and the manufacturer's 6, 12 and 36-month maintenance schedule, based on the manufacturer's manual.

Desiccant Dehumidification · 2 November 2026
AD Series Troubleshooting4:00
Service & Maintenance
AD Series Troubleshooting

We go through the most common fault symptoms on an AD series silica gel rotor dehumidifier and the first checks to make before calling service: unit will not start, has stopped, stopped in automatic or remote mode, lost capacity, tripped fuses, white service light, rotor not turning and low airflow. For any alarm not covered here, call the authorised service.

Desiccant Dehumidification · 2 November 2026
Setting Up a Portable Dehumidifier4:23
Service & Maintenance
Setting Up a Portable Dehumidifier

A wheeled refrigerant dehumidifier works in warehouses, factories and on building sites, and where it stands matters as much as its capacity. In this episode we cover taking delivery of a heavy-duty industrial portable dehumidifier, positioning it in a warehouse, condensate options, the electrical connection and first start-up, based on the manufacturer's manual.

Portable Dehumidification · 1 November 2026
Maintaining a Portable Dehumidifier3:44
Service & Maintenance
Maintaining a Portable Dehumidifier

Maintaining a wheeled refrigerant dehumidifier is simple, but if it is skipped, capacity drops and the unit is put under strain. In this episode we cover how often and how to clean the filter, condenser cleaning, what the four control panel lights mean, the defrost cycle, and what to check when the unit does not start or collects no water, based on the manufacturer's manual.

Portable Dehumidification · 1 November 2026
Maintaining a Pool Dehumidifier4:01
Service & Maintenance
Maintaining a Pool Dehumidifier

A pool dehumidifier runs almost all year in warm, humid, chlorinated air; when maintenance slips, capacity drops first, then humidity rises and condensation appears on the walls. This episode covers what to do, and how often, for a wall-mounted pool dehumidifier: safety, monthly filter cleaning, removing the cover, daily use, the annual service checklist, shock chlorination, summer shutdown and the symptoms that need a service visit.

Pool Dehumidification · Maintenance · 1 November 2026