SERVICE & MAINTENANCEDesiccant Dehumidification
AD Series Troubleshooting
We go through the most common fault symptoms on an AD series silica gel rotor dehumidifier and the first checks to make before calling service: unit will not start, has stopped, stopped in automatic or remote mode, lost capacity, tripped fuses, white service light, rotor not turning and low airflow. For any alarm not covered here, call the authorised service.
Published: 2 November 2026Narration: Turkish and English4:00
In this video
- Faults are signalled by the red light on the front panel and the cause appears on the alarm page of the display. For any alarm not listed, call the authorised service.
- If the unit will not start, check the control fuses, the external start signal, the front door micro-switch, the main fuses and the phase sequence.
- A unit stopped in automatic mode is often not faulty; humidity has fallen below the set point. In remote mode, check the external start contact.
- If capacity has dropped, check the filters, airflows and dampers, the rotor belt, air leaks past the seals and the regeneration heater (on steam units the valve, pressure and condensate trap).
- If the rotor is not turning, the belt is the usual cause: check a slipping belt's tension and replace a broken one. Fan, gear motor and heater alarms are reset by hand on the display once the cause is fixed.
More from this series
Service & Maintenance
Installing an AD Series Dehumidifier
Desiccant Dehumidification · 2 November 2026
Service & Maintenance
Commissioning the AD Series
Desiccant Dehumidification · 2 November 2026
Service & Maintenance
AD Series Periodic Maintenance
Desiccant Dehumidification · 2 November 2026
Service & Maintenance
Setting Up a Portable Dehumidifier
Portable Dehumidification · 1 November 2026
Service & Maintenance
Maintaining a Portable Dehumidifier
Portable Dehumidification · 1 November 2026
Service & Maintenance
Maintaining a Pool Dehumidifier
Pool Dehumidification · Maintenance · 1 November 2026