Dehumidifier Selection
Selecting an industrial dehumidifier is never just a single capacity figure. This episode covers eight criteria, from target relative humidity and dew point, moisture load and technology to reactivation energy, casing, automation and service, and a five-step decision process.
In this video
- Selection starts with the target RH and dew point; a condensing unit cannot go much below a +5 °C dew point and works best above +10 °C.
- Capacity is set by the moisture load, not the air change rate; seven moisture sources are calculated one by one, and a 20% margin is enough.
- For a dew point target above +10 °C in a 15–35 °C space, choose condensing; below +5 °C a desiccant rotor is needed, and in between the two are compared on energy.
- The reactivation source follows the site infrastructure: with a boiler, steam pays back in 6–10 months; 80–120 °C waste heat preheats the reactivation air, and natural gas also saves significantly over electricity.
- The casing follows the environment: galvanised steel, AISI 304 or 316L stainless, chlorine-resistant casings with coated coils for pools and ATEX for explosive atmospheres.
More from this series
Selecting an industrial dehumidifier starts with an accurate moisture load calculation.
We usually judge indoor comfort by temperature alone, yet relative humidity shapes our health, productivity and the life of the building just as much.
There are three main technologies for industrial dehumidification: desiccant rotor, condensing and pool units.
In winter, heated indoor air can drop below 15% relative humidity.
In an indoor pool, the heated water surface evaporates all day; this evaporation cannot be prevented, only controlled.
Both steam humidifier technologies use about 0.75 kWh per kilogram of steam; the difference lies in water quality, control accuracy and maintenance.
More videos
The AD series are silica gel rotor industrial dehumidifiers that run continuously in production areas and warehouses where low humidity is needed.
How well an AD series silica gel rotor dehumidifier performs on site depends on the checks made at first start-up and on correctly set airflows.
AD series silica gel rotor dehumidifiers depend on regular maintenance to run efficiently.