Humidity Control in Glass Lamination

In laminated glass, how well the PVB interlayer bonds to the glass is often decided by the air in the production room; film moisture of about 0.4% at 30% relative humidity exceeds 2% at 80%. This episode covers the moisture balance of PVB film, the pummel test, lay-up room conditions, the dew point target of around 0 °C and why silica gel rotor dehumidification is needed to reach it.

Published: 8 October 2026Narration: Turkish and English6:26

In this video

  • The room's relative humidity sets the moisture of the PVB interlayer: film moisture is about 0.4% at 30% RH but exceeds 2% at 80%, while manufacturers recommend about 0.4–0.5% for lamination.
  • Film that is too moist leads to bubbles, edge separation and haze; film that is too dry leads to excessive adhesion, brittleness under impact and static. The aim is to hold humidity steady within a narrow band.
  • Adhesion is scored from 0 to 10 with the pummel test; architectural glass usually targets 3–7, and steady room humidity means a steady pummel value.
  • The most common lay-up room condition is 18–20 °C and 25–30% RH; its dew point of about −2 to +2 °C lies outside the practical limit of condensing units.
  • A silica gel rotor unit works comfortably at this dew point; a cooling coil ahead of the rotor takes the summer load economically, and steam or gas reactivation typically cuts operating costs by 40–60%.

Related

More from this series

Moisture Load Calculation4:12
Academy Series · Ep. 1
Moisture Load Calculation

Selecting an industrial dehumidifier starts with an accurate moisture load calculation. This episode walks through the seven moisture sources, a worked infiltration example and how the target dew point drives the choice of technology.

Psychrometrics & Sizing · 4 October 2026
Relative Humidity and Health4:58
Academy Series · Ep. 2
Relative Humidity and Health

We usually judge indoor comfort by temperature alone, yet relative humidity shapes our health, productivity and the life of the building just as much. This episode uses the Sterling chart to cover the effects of low and high humidity, the ideal range and how humidity is controlled in both directions.

Health & Indoor Climate · 3 October 2026
Dehumidification Technologies4:59
Academy Series · Ep. 3
Dehumidification Technologies

There are three main technologies for industrial dehumidification: desiccant rotor, condensing and pool units. This episode compares their operating principles, achievable dew points, strengths and limits, and shows how the target dew point and the ambient temperature drive the right choice.

Technology Selection · 4 October 2026
Dehumidifier Selection4:52
Academy Series · Ep. 4
Dehumidifier Selection

Selecting an industrial dehumidifier is never just a single capacity figure. This episode covers eight criteria, from target relative humidity and dew point, moisture load and technology to reactivation energy, casing, automation and service, and a five-step decision process.

Equipment Selection · 4 October 2026
How to Calculate Humidification Load5:46
Academy Series · Ep. 5
How to Calculate Humidification Load

In winter, heated indoor air can drop below 15% relative humidity. This episode calculates the humidification load step by step from the absolute humidity difference and the volume of air entering the space, works through two examples with Türkiye climate data, and covers economisers, unit selection and the energy budget.

Humidification Load · 5 October 2026
Humidity Control in Swimming Pools5:14
Academy Series · Ep. 6
Humidity Control in Swimming Pools

In an indoor pool, the heated water surface evaporates all day; this evaporation cannot be prevented, only controlled. This episode calculates evaporation with the VDI 2089 formula, works through a 32 m² villa pool example, and covers hall conditions, chloramines and corrosion, unit selection, air distribution and maintenance.

Pool Humidity Control · 5 October 2026