Dehumidification in Cooling Tunnels
In chocolate and confectionery production, gloss is often lost at the end of the cooling tunnel. If the cold product surface is below the dew point of the tunnel air or the room air at the exit, moisture condenses on it and sugar bloom begins. This episode covers where condensation begins, why relative humidity can mislead, dew point targets by product, the buffer zone at the exit, infiltration, a worked moisture load and dry-air flow, and choosing the right dehumidification technology.
In this video
- Condensation starts where the product surface is coldest, at the end of the tunnel and at the exit; the air dew point is kept at least 3 degrees below the lowest product surface temperature.
- A water film on the surface dissolves sugar, which then recrystallises as coarse crystals (sugar bloom); fat bloom comes from temperature swings, not humidity.
- For coated chocolate the dew point is held at +4 °C at most, preferably +2 °C; +6 °C for tablets and +2 °C for pralines and filled products. A buffer zone at 18 °C and 45% RH, with a dew point of about +6 °C, prevents condensation at the exit.
- In a 32 m example tunnel with two openings, a +2 °C target and 32 °C / 75% summer air, the total moisture load is 27.5 kg/h including a 20% margin; supply air at a −20 °C dew point needs about 6,400 m³/h of dry air.
- Almost all of the load comes through the openings, so strip curtains, air curtains and 5–20 Pa positive pressure also shrink the unit. These targets lie below the +5 °C limit of condensing units, so a silica gel rotor or hybrid system is needed.
More from this series
Selecting an industrial dehumidifier starts with an accurate moisture load calculation.
We usually judge indoor comfort by temperature alone, yet relative humidity shapes our health, productivity and the life of the building just as much.
There are three main technologies for industrial dehumidification: desiccant rotor, condensing and pool units.
Selecting an industrial dehumidifier is never just a single capacity figure.
In winter, heated indoor air can drop below 15% relative humidity.
In an indoor pool, the heated water surface evaporates all day; this evaporation cannot be prevented, only controlled.
More videos
The AD series are silica gel rotor industrial dehumidifiers that run continuously in production areas and warehouses where low humidity is needed.
How well an AD series silica gel rotor dehumidifier performs on site depends on the checks made at first start-up and on correctly set airflows.
AD series silica gel rotor dehumidifiers depend on regular maintenance to run efficiently.