Humidity Balance in Cheese Maturation

One kilogram of kaşar cheese takes about 10 kilograms of milk; to get the full return on it, the air in the maturation room must be managed correctly. This episode covers rind formation, the risks of cracking and condensation, mould and hygiene, drying and maturation room conditions, and choosing the right dehumidification technology by dew point.

Published: 6 October 2026Narration: Turkish and English6:20

In this video

  • In kaşar cheese, humidity control becomes critical mainly after salting, in the surface drying and maturation stages; the quality of a healthy rind is decided by the air in the first few days.
  • Above 0.5 m/s at shelf level, fine cracks appear in the rind; the aim is an even flow of 20–40 cm/s over every product surface.
  • If the product surface is colder than the dew point of the air, condensation begins: air at 13 °C and 90% RH has a dew point of about 11.4 °C.
  • Typical conditions are 12–16 °C and 80–85% RH for surface drying and 10–14 °C and 85–90% RH for maturation; the exact values are set by the product recipe.
  • With dew points of about 7.6–13.5 °C, these rooms sit on the boundary between two technologies; in maturation rooms condensing, rotor and hybrid options are compared on energy use, and below a 5 °C dew point the clear choice is a silica gel rotor.

Related

More from this series

Moisture Load Calculation4:12
Academy Series · Ep. 1
Moisture Load Calculation

Selecting an industrial dehumidifier starts with an accurate moisture load calculation. This episode walks through the seven moisture sources, a worked infiltration example and how the target dew point drives the choice of technology.

Psychrometrics & Sizing · 4 October 2026
Relative Humidity and Health4:58
Academy Series · Ep. 2
Relative Humidity and Health

We usually judge indoor comfort by temperature alone, yet relative humidity shapes our health, productivity and the life of the building just as much. This episode uses the Sterling chart to cover the effects of low and high humidity, the ideal range and how humidity is controlled in both directions.

Health & Indoor Climate · 3 October 2026
Dehumidification Technologies4:59
Academy Series · Ep. 3
Dehumidification Technologies

There are three main technologies for industrial dehumidification: desiccant rotor, condensing and pool units. This episode compares their operating principles, achievable dew points, strengths and limits, and shows how the target dew point and the ambient temperature drive the right choice.

Technology Selection · 4 October 2026
Dehumidifier Selection4:52
Academy Series · Ep. 4
Dehumidifier Selection

Selecting an industrial dehumidifier is never just a single capacity figure. This episode covers eight criteria, from target relative humidity and dew point, moisture load and technology to reactivation energy, casing, automation and service, and a five-step decision process.

Equipment Selection · 4 October 2026
How to Calculate Humidification Load5:46
Academy Series · Ep. 5
How to Calculate Humidification Load

In winter, heated indoor air can drop below 15% relative humidity. This episode calculates the humidification load step by step from the absolute humidity difference and the volume of air entering the space, works through two examples with Türkiye climate data, and covers economisers, unit selection and the energy budget.

Humidification Load · 5 October 2026
Humidity Control in Swimming Pools5:14
Academy Series · Ep. 6
Humidity Control in Swimming Pools

In an indoor pool, the heated water surface evaporates all day; this evaporation cannot be prevented, only controlled. This episode calculates evaporation with the VDI 2089 formula, works through a 32 m² villa pool example, and covers hall conditions, chloramines and corrosion, unit selection, air distribution and maintenance.

Pool Humidity Control · 5 October 2026

More videos

← All videos